Windy City Wire 042003

P/N 042003 - Lo-Capacitance, 24 AWG, 2 Pair Each Pair Shielded, 12.5 pF, 100 Ohm, Plenum



View as a PDF Document

Cable Specifications

Description: 2 Pair, 24 AWG Tinned Copper Individually Shielded Pairs RS-232, RS-422 Low-Capacitance Communication, Instrumentation and Special Application Plenum Cable
Conductor Description: 24 AWG (7/32) Tinned Copper, OD: .024" Nom.
Insulation: Foam FEP; OD: .054" +-.002"
Color Code: Pair 1: White/Blue, Blue/White Pair 2: White/Orange Orange/White
Shield: Aluminum/Polyester-25% Overlap-Foil Out
Drain Wire: 24 AWG Stranded Tinned Copper
Jacket: Low-Smoke Plenum Rated PVC
Marking: TEMPERATURE CONTROL SYSTEM LOW CAP 12.5 pF, ZONE BUS / COMM A B C D E 0 1 2 3 4 5 6 7 8 924 AWG Shielded Type CMP (UL) 75C
Overall Diameter: .235" Nom.
Conductor DCR: 26.8 Ohms/Mft. Max.
Capacitance: 12.5 pF/ft. Nom. (Mutual), 23.0 pF/ft. Nom. (Cond-
Impedance: 100 Ohms Nom.
Velocity of Propagation: 82%
Temperature and Voltage Rating: -10 C to 75 C / 300 Volts Max.
Cable Weight: 23 Lbs/Mft.

Flame Rating:
Approved for Plenum use without conduit per NEC Article 800 by passing UL-910 Steiner Tunnel test (USA).

Agencies Approvals:
UL Subject 444 and NEC Article 800 Type CMP Communication Cable.
   